10 AWG Ampacity
NEC Table 310.16 values for 10 AWG copper and aluminum, the 30 A small-conductor rule for copper, and typical 30 A circuit applications.
Table ampacity for 10 AWG
Under NEC Table 310.16 (≤3 current-carrying conductors in a raceway, cable, or earth, 30°C ambient):
| Conductor | 60°C | 75°C | 90°C | 240.4(D) OCPD max |
|---|---|---|---|---|
| 10 AWG copper | 30 A | 35 A | 40 A | 30 A |
| 10 AWG aluminum or copper-clad aluminum | 25 A | 30 A | 35 A | 25 A |
NEC 240.4(D) generally limits overcurrent protection for 10 AWG copper to 30 A, even though the 75°C and 90°C columns list 35 A and 40 A. 10 AWG aluminum is generally limited to 25 A by the same rule. Type NM-B uses the 60°C column (334.80), so 10 AWG copper NM-B is 30 A under the base conditions.
Typical applications
10 AWG copper is widely used on 30 A branch circuits for household electric water heaters, some window air conditioners, clothes dryers in older or specific installations, and certain RV or appliance circuits. Many electric ranges and larger HVAC loads require a larger conductor; always size from the nameplate, the appliance instructions, and the adopted code — not from a typical-use list.
10 AWG is approximately 5.26 mm². For a 20 A circuit, 10 AWG copper is larger than the usual 12 AWG copper minimum and is sometimes chosen for voltage drop on a long run. See the voltage drop calculator and 12 AWG ampacity.
Disclaimer: This site is a general reference only. It is not a substitute for the adopted electrical code, manufacturer instructions, or the judgment of a licensed electrician. Ampacity, overcurrent protection, voltage drop, and conduit fill depend on conductor type, temperature rating, ambient temperature, the number of current-carrying conductors, termination ratings, installation method, and local amendments. Always verify figures in the edition of the code that applies to your work.