Wire Color Codes (US, UK & EU)

Separate identification tables for United States NEC practice, United Kingdom BS 7671 (current and older colors), and the EU/IEC palette — so regional rules are not combined into a single color list.

Use the table for the region that applies

Conductor color is not a single worldwide rule. The United States (NEC), the United Kingdom (BS 7671, including the older UK palette), and the EU/IEC identification system are presented here in separate tables so they are not mixed into one set of colors. Always identify conductors by the standard that applies at the installation, and by testing, not by color memory alone — especially in buildings that have been rewired more than once.

United States (NEC / NFPA 70)

The NEC is strict about grounded conductors, grounding conductors, and certain special identifications. It is much less prescriptive about the exact color of ordinary ungrounded (hot) phase conductors, other than forbidding the reserved colors. Common 120/208 V and 277/480 V palettes used in the trade are conventions unless a specific section requires a color (notably the orange high-leg).

FunctionRequired or conventional identificationNotes
Equipment grounding conductorGreen, green with a yellow stripe, or bareReserved in the NEC for grounding. Do not use these identifications for ungrounded or grounded circuit conductors.
Grounded conductor (neutral)White or gray, or three continuous white stripes on other than green insulation (as permitted by size/type)Reserved for the grounded conductor. A white or gray conductor may be re-identified as a hot only where the Code specifically allows it (for example certain cable assemblies in switch loops, with proper marking).
Ungrounded conductors (hots)Any color other than white, gray, green, or green with yellowThe NEC does not generally mandate black/red/blue versus brown/orange/yellow.
120/240 V single-phase (common practice)Black (L1), red (L2), white (neutral), green or bare (ground)Convention, widely used in dwellings.
120/208 V, three-phase (common practice)Black, red, blue; white or gray neutral; green/bare groundConvention in many commercial buildings.
277/480 V, three-phase (common practice)Brown, orange, yellow; gray often used for the 480/277 V neutralConvention. A gray neutral must still meet grounded-conductor identification rules and be distinguished from a white 120/208 V neutral where both systems are present.
High-leg (wild-leg) deltaOrange for the high-legRequired identification where this system is used (see NEC 110.15 and related marking rules).

United Kingdom — current colors (BS 7671, harmonized)

Since the mid-2000s (BS 7671:2008 and later practice following the 2004/2006 harmonization), UK fixed wiring uses the IEC palette. These are the colors now expected in new installations:

FunctionColor (current BS 7671 / IEC)
Line, single-phase (L)Brown
Neutral (N)Blue
Protective earth (PE)Green-and-yellow
Line 1 (L1), three-phaseBrown
Line 2 (L2), three-phaseBlack
Line 3 (L3), three-phaseGrey

United Kingdom — older (pre-harmonization) colors

Older UK installations used a different palette. These colors may still be present in existing wiring and must not be read as if they were the current IEC set. In particular, old UK black was the neutral, whereas current black is a phase (L2).

FunctionOlder UK color (do not mix with the table above)
Line, single-phase (live)Red
NeutralBlack
EarthGreen-and-yellow (earlier practice used green alone in some historic work)
Three-phase linesRed, yellow, and blue
Three-phase neutralBlack

EU / IEC identification (IEC 60445, HD 308)

The harmonized European identification for AC power conductors is the same palette now used in current UK practice. It should be treated as its own standard, not as a US rule and not as the old UK rule.

FunctionIEC / typical EU color
Protective earth (PE)Green-and-yellow
Neutral (N)Blue
Line, single-phase (L)Brown
L1 / L2 / L3Brown / black / grey

Control, DC, and data cables often use other identification systems. Confirm the product standard and the documentation for the installation rather than assuming AC power colors apply.

Disclaimer: This site is a general reference only. It is not a substitute for the adopted electrical code, manufacturer instructions, or the judgment of a licensed electrician. Ampacity, overcurrent protection, voltage drop, and conduit fill depend on conductor type, temperature rating, ambient temperature, the number of current-carrying conductors, termination ratings, installation method, and local amendments. Always verify figures in the edition of the code that applies to your work.