AWG to mm² Conversion Chart
Approximate square-millimeter areas and solid-conductor diameters for standard American Wire Gauge and kcmil sizes, for comparison with metric conductor cross-sections.
Standard AWG to mm² values
American Wire Gauge (AWG) is a logarithmic size system used mainly in North America. Area in square millimeters is the SI figure most often compared with IEC 60228 conductor classes. The mm² values below are the generally published approximations (rounded) that correspond to the nominal circular-mil area of each AWG size. They are not a guarantee that a particular manufactured cable will measure exactly that area.
Solid-conductor bare diameters follow the AWG definition commonly associated with ASTM B258. Stranded conductors have a larger overall diameter than the solid size of the same AWG. kcmil sizes are listed by nominal thousand circular mils, not by AWG number.
| Size (AWG / kcmil) | Solid diameter (in) | Solid diameter (mm) | Nominal area (circular mils) | Approx. area (mm²) |
|---|---|---|---|---|
| 24 | 0.0201 | 0.511 | 404 | 0.205 |
| 22 | 0.0253 | 0.644 | 640 | 0.326 |
| 20 | 0.0320 | 0.812 | 1,020 | 0.519 |
| 18 | 0.0403 | 1.024 | 1,620 | 0.823 |
| 16 | 0.0508 | 1.291 | 2,580 | 1.31 |
| 14 | 0.0641 | 1.628 | 4,110 | 2.08 |
| 12 | 0.0808 | 2.053 | 6,530 | 3.31 |
| 10 | 0.1019 | 2.588 | 10,380 | 5.26 |
| 8 | 0.1285 | 3.264 | 16,510 | 8.37 |
| 6 | 0.1620 | 4.115 | 26,240 | 13.3 |
| 4 | 0.2043 | 5.189 | 41,740 | 21.2 |
| 3 | 0.2294 | 5.827 | 52,620 | 26.7 |
| 2 | 0.2576 | 6.544 | 66,360 | 33.6 |
| 1 | 0.2893 | 7.348 | 83,690 | 42.4 |
| 1/0 | 0.3249 | 8.252 | 105,600 | 53.5 |
| 2/0 | 0.3648 | 9.266 | 133,100 | 67.4 |
| 3/0 | 0.4096 | 10.40 | 167,800 | 85.0 |
| 4/0 | 0.4600 | 11.68 | 211,600 | 107 |
| 250 kcmil | — | — | 250,000 | 127 |
| 300 kcmil | — | — | 300,000 | 152 |
| 350 kcmil | — | — | 350,000 | 177 |
| 400 kcmil | — | — | 400,000 | 203 |
| 500 kcmil | — | — | 500,000 | 253 |
| 600 kcmil | — | — | 600,000 | 304 |
| 750 kcmil | — | — | 750,000 | 380 |
| 1000 kcmil | — | — | 1,000,000 | 507 |
Frequently used branch-circuit sizes: 14 AWG ≈ 2.08 mm², 12 AWG ≈ 3.31 mm², 10 AWG ≈ 5.26 mm², 8 AWG ≈ 8.37 mm², 6 AWG ≈ 13.3 mm², and 4 AWG ≈ 21.2 mm².
How to use this chart
Cross-section alone does not determine ampacity. A 2.5 mm² IEC conductor and a 14 AWG (2.08 mm²) conductor are close in area but are not interchangeable for code compliance, temperature rating, or overcurrent protection. For current-carrying capacity, use the NEC ampacity chart or the applicable IEC/BS 7671 tables for the cable type.
If you also need to check voltage drop or raceway fill, continue to the voltage drop calculator or the conduit fill calculator. Overall insulated diameter — not bare metal diameter — is what matters for conduit fill.
Disclaimer: This site is a general reference only. It is not a substitute for the adopted electrical code, manufacturer instructions, or the judgment of a licensed electrician. Ampacity, overcurrent protection, voltage drop, and conduit fill depend on conductor type, temperature rating, ambient temperature, the number of current-carrying conductors, termination ratings, installation method, and local amendments. Always verify figures in the edition of the code that applies to your work.