Wire Size Chart (AWG Ampacity)
A practical copper wire size chart combining approximate metric area, NEC ampacity at 60°C, 75°C, and 90°C, and the small-conductor overcurrent limits used on everyday branch circuits.
Copper AWG size, area, and ampacity
This chart brings together nominal metric area and the copper ampacities from NEC Table 310.16 so you can see size, current, and typical branch-circuit practice in one place. Ampacity conditions are the Table 310.16 base conditions: not more than three current-carrying conductors in a raceway, cable, or earth, 30°C ambient. The overcurrent column reflects NEC 240.4(D) for 14, 12, and 10 AWG copper. Larger sizes are protected according to their allowable ampacity and termination ratings (110.14(C)), not the small-conductor rule.
| Copper size | Approx. mm² | 60°C A | 75°C A | 90°C A | Typical max OCPD (see notes) | Common use (illustrative) |
|---|---|---|---|---|---|---|
| 14 AWG | 2.08 | 15 | 20 | 25 | 15 A | 15 A lighting and general branch circuits (copper) |
| 12 AWG | 3.31 | 20 | 25 | 30 | 20 A | Typical 20 A general-purpose receptacles (copper) |
| 10 AWG | 5.26 | 30 | 35 | 40 | 30 A | Typical 30 A appliances, water heaters, window AC (copper) |
| 8 AWG | 8.37 | 40 | 50 | 55 | Table ampacity / 110.14(C) | Ranges, larger appliances, feeders — confirm terminations |
| 6 AWG | 13.3 | 55 | 65 | 75 | Table ampacity / 110.14(C) | Cooktops, feeders, subpanels — confirm terminations |
| 4 AWG | 21.2 | 70 | 85 | 95 | Table ampacity / 110.14(C) | Feeders and larger loads |
| 2 AWG | 33.6 | 95 | 115 | 130 | Table ampacity / 110.14(C) | Feeders and service conductors (as applicable) |
| 1/0 AWG | 53.5 | 125 | 150 | 170 | Table ampacity / 110.14(C) | Larger feeders |
| 2/0 AWG | 67.4 | 145 | 175 | 195 | Table ampacity / 110.14(C) | Larger feeders |
| 3/0 AWG | 85.0 | 165 | 200 | 225 | Table ampacity / 110.14(C) | Larger feeders / services as applicable |
| 4/0 AWG | 107 | 195 | 230 | 260 | Table ampacity / 110.14(C) | Larger feeders / services as applicable |
“Typical use” descriptions are examples of how these sizes appear in US residential and light-commercial work. They are not a substitute for a load calculation or the adopted code.
Choosing a column and a breaker
For most 15 A and 20 A copper branch circuits in NM-B cable, the practical result is 14 AWG on a 15 A breaker and 12 AWG on a 20 A breaker. That combination comes from 240.4(D) together with the 60°C limit that applies to Type NM-B under 334.80. A 12 AWG THHN conductor in conduit may have a 25 A or 30 A table ampacity, but 240.4(D) still generally keeps the overcurrent device at 20 A for that conductor size.
See also the full ampacity chart (copper and aluminum), 20 amp breaker wire size, and the wire size calculator when voltage drop or continuous loading may require a larger conductor than the breaker size alone would suggest.
Disclaimer: This site is a general reference only. It is not a substitute for the adopted electrical code, manufacturer instructions, or the judgment of a licensed electrician. Ampacity, overcurrent protection, voltage drop, and conduit fill depend on conductor type, temperature rating, ambient temperature, the number of current-carrying conductors, termination ratings, installation method, and local amendments. Always verify figures in the edition of the code that applies to your work.