Conduit Fill Calculator
A client-side calculator that totals THHN/THWN-2 conductor area and compares it with NEC Chapter 9 conduit-fill limits for EMT and PVC Schedule 40.
Calculate conduit fill
Fill is compared with NEC Chapter 9, Table 1:
- 1 conductor: maximum 53% of the conduit’s internal cross-section
- 2 conductors: maximum 31%
- Over 2 conductors: maximum 40%
Conductor areas are the approximate areas for Type THHN / THWN / THWN-2 from Chapter 9, Table 5. Conduit internal areas are from Chapter 9, Table 4, for EMT and PVC Schedule 40. Add a row for each size you will pull, including equipment grounding conductors when they occupy the raceway.
Assumptions
This tool uses the published Table 4 internal areas and Table 5 THHN/THWN/THWN-2 approximate areas. It does not include compact conductors, other insulation types, or boxes and fittings. A conduit nipple 24 inches or less may be filled to 60% under Chapter 9, Note 4 to Table 1; that exception is not applied automatically. Meeting fill is separate from meeting ampacity adjustment when more than three current-carrying conductors share a raceway.
For current-carrying capacity after you choose a raceway, return to the ampacity chart or the wire size calculator.
Disclaimer: This site is a general reference only. It is not a substitute for the adopted electrical code, manufacturer instructions, or the judgment of a licensed electrician. Ampacity, overcurrent protection, voltage drop, and conduit fill depend on conductor type, temperature rating, ambient temperature, the number of current-carrying conductors, termination ratings, installation method, and local amendments. Always verify figures in the edition of the code that applies to your work.