14 AWG Ampacity

How much current 14 AWG copper can carry under NEC Table 310.16, and why a 14 AWG copper conductor is generally protected at 15 A.

Table ampacity for 14 AWG copper

Under NEC Table 310.16 (not more than three current-carrying conductors in a raceway, cable, or earth, 30°C ambient), 14 AWG copper is listed at:

Conductor60°C75°C90°C
14 AWG copper15 A20 A25 A

Those higher 75°C and 90°C values do not authorize a 20 A breaker on 14 AWG copper in ordinary branch-circuit use. NEC 240.4(D) generally limits overcurrent protection for 14 AWG copper to 15 A. Type NM-B (often used in dwellings) is also limited to the 60°C column by NEC 334.80, which is 15 A for 14 AWG copper.

Typical applications

14 AWG copper is the usual conductor for 15 A general lighting and 15 A receptacle circuits in US dwelling work, where the load and voltage drop allow it. It is not the typical size for a 20 A kitchen, bathroom, laundry, or general-purpose 20 A receptacle circuit — those are usually 12 AWG copper. See 12 AWG ampacity and 20 amp breaker wire size.

14 AWG is approximately 2.08 mm². That is close to, but not the same as, a 2.5 mm² IEC conductor; do not treat the sizes as code-equivalent. Approximate area is listed on the AWG to mm² chart.

Disclaimer: This site is a general reference only. It is not a substitute for the adopted electrical code, manufacturer instructions, or the judgment of a licensed electrician. Ampacity, overcurrent protection, voltage drop, and conduit fill depend on conductor type, temperature rating, ambient temperature, the number of current-carrying conductors, termination ratings, installation method, and local amendments. Always verify figures in the edition of the code that applies to your work.