RCD Types

A reference to residual current device types used in BS 7671 and IEC practice — Type AC, A, F, and B — classified by the residual-current waveforms they are designed to detect.

What an RCD does

A residual current device (RCD) disconnects a circuit when the residual (unbalanced) current exceeds a trip threshold. In IEC and BS 7671 practice, a 30 mA RCD is widely used for additional protection against electric shock. Higher ratings such as 100 mA or 300 mA appear in fire-protection or distribution applications, often with time-delay (Type S / selective) characteristics so downstream 30 mA devices trip first.

RCDs are classified by the waveform of residual current they can detect. That is a different question from their mA rating or whether they are a breaker-style RCCB, an RCBO (RCD plus overcurrent), or a socket-outlet device. The type letters below follow IEC 60755 / IEC 61008 / IEC 61009 practice as used in BS 7671.

Type AC, A, F, and B

TypeDetects (summary)Typical context
Type ACSinusoidal alternating residual current onlyLegacy general-purpose use on simple AC loads. In the UK, BS 7671:2018 Amendment 2 generally no longer allows Type AC RCDs for most new installations, because many modern electronic loads produce residual current that Type AC may not detect reliably.
Type ASinusoidal AC plus pulsating DC residual currentThe usual general-purpose choice for circuits supplying electronic equipment with rectifiers (many appliances, LED drivers, IT power supplies, and similar single-phase loads).
Type FType A capability plus residual currents with mixed frequencies, as specified for single-phase frequency invertersOften considered for single-phase variable-speed drives, heat pumps, washing machines, and similar inverter loads, in accordance with the product and wiring-rules guidance.
Type BType A capability plus smooth DC residual current and residual currents from three-phase inverters, within the standard’s defined rangeUsed where smooth DC fault current is possible, including many electric-vehicle charging installations, some photovoltaic inverters, and certain three-phase variable-speed drives or medical-equipment supplies. Specific product standards (for example EV charging) may require Type B or an equivalent protective measure.

Other markings you may see include Type B+ or manufacturer-specific variants with a stated DC frequency range, and S (selective / time-delayed) devices for coordination. Those markings are additional to, not a replacement for, the AC/A/F/B waveform type.

BS 7671 and IEC practice notes

Selection is based on the nature of the residual current the connected equipment can produce, the required sensitivity (often 30 mA for additional protection of socket-outlets and bathroom circuits), and selectivity with upstream devices. A Type AC device must not be assumed to be adequate for modern electronic loads. Conversely, Type B is not automatically required on every circuit; it is specified where smooth DC or the relevant inverter residual currents are expected, or where a product standard requires it.

US NEC GFCI devices (typically Class A, 4–6 mA) are a related idea — residual/ground-fault protection for persons — but they are not selected by IEC Type AC/A/F/B letters. See GFCI vs AFCI for the US devices.

Disclaimer: This site is a general reference only. It is not a substitute for the adopted electrical code, manufacturer instructions, or the judgment of a licensed electrician. Ampacity, overcurrent protection, voltage drop, and conduit fill depend on conductor type, temperature rating, ambient temperature, the number of current-carrying conductors, termination ratings, installation method, and local amendments. Always verify figures in the edition of the code that applies to your work.