Wire Size Calculator
A client-side tool that compares NEC Table 310.16 ampacity with a voltage-drop target and reports the larger of the two minimum sizes.
Estimate a minimum conductor size
This calculator compares your load with two independent checks and reports the larger of the two sizes:
- Ampacity: the smallest size whose NEC Table 310.16 value in the temperature column you select is at least the design current (optionally 125% if you mark the load continuous).
- Voltage drop: the smallest size whose calculated drop, using the same 75°C K-factor formulas as the voltage drop calculator, is within your percentage target.
Assumptions
Ampacities are the published Table 310.16 values for not more than three current-carrying conductors in a raceway, cable, or earth, 30°C ambient. No ambient correction or bundling adjustment is applied. The 60°C column is the correct starting point for Type NM-B allowable ampacity (NEC 334.80). Selecting the 90°C column does not override termination limits in 110.14(C) or the small-conductor overcurrent limits in 240.4(D). Voltage drop uses K = 12.9 (copper) or 21.2 (aluminum) at 75°C, with D in feet and nominal circular mils. A 3% target is a common design note, not a universal Code mandate.
Disclaimer: This site is a general reference only. It is not a substitute for the adopted electrical code, manufacturer instructions, or the judgment of a licensed electrician. Ampacity, overcurrent protection, voltage drop, and conduit fill depend on conductor type, temperature rating, ambient temperature, the number of current-carrying conductors, termination ratings, installation method, and local amendments. Always verify figures in the edition of the code that applies to your work.