12 AWG Ampacity
NEC Table 310.16 values for 12 AWG, the 20 A small-conductor rule for copper, and why 12 AWG copper is the usual wire size for a 20 A branch circuit.
Table ampacity for 12 AWG
Under NEC Table 310.16 (≤3 current-carrying conductors in a raceway, cable, or earth, 30°C ambient):
| Conductor | 60°C | 75°C | 90°C | 240.4(D) OCPD max |
|---|---|---|---|---|
| 12 AWG copper | 20 A | 25 A | 30 A | 20 A |
| 12 AWG aluminum or copper-clad aluminum | 15 A | 20 A | 25 A | 15 A |
The copper 75°C and 90°C columns are higher than 20 A, but NEC 240.4(D) generally still limits the overcurrent device on 12 AWG copper to 20 A. That is why a 20 A breaker is paired with 12 AWG copper in typical branch-circuit work, not because the 90°C column is unused for other calculations such as adjustment factors.
12 AWG aluminum is generally limited to a 15 A overcurrent device by 240.4(D). A 20 A aluminum branch circuit therefore requires a larger aluminum conductor (commonly 10 AWG, which 240.4(D) limits to 25 A). Confirm terminations, connector listings, and the adopted code before substituting aluminum for copper.
NM-B, terminations, and voltage drop
Type NM-B must use the 60°C column for allowable ampacity (NEC 334.80), so 12 AWG copper NM-B is 20 A under the base table conditions. Continuous loads on a 20 A circuit are generally limited to 16 A (125% sizing in 210.19 and 210.20). Long runs may need a larger conductor for voltage drop even when 12 AWG meets ampacity; use the voltage drop calculator or wire size calculator.
12 AWG is approximately 3.31 mm². See also 20 amp breaker wire size and 10 AWG ampacity.
Disclaimer: This site is a general reference only. It is not a substitute for the adopted electrical code, manufacturer instructions, or the judgment of a licensed electrician. Ampacity, overcurrent protection, voltage drop, and conduit fill depend on conductor type, temperature rating, ambient temperature, the number of current-carrying conductors, termination ratings, installation method, and local amendments. Always verify figures in the edition of the code that applies to your work.