20 Amp Breaker Wire Size

In typical US branch-circuit practice, a 20 A overcurrent device is paired with 12 AWG copper. The reasons are in NEC 240.4(D) and the ampacity table conditions — not a rule of thumb alone.

The usual answer: 12 AWG copper

For a 20 A breaker or fuse protecting a copper branch-circuit conductor, the typical minimum size is 12 AWG copper. NEC 240.4(D) generally limits 14 AWG copper to a 15 A overcurrent device and 12 AWG copper to 20 A. Putting 14 AWG copper on a 20 A breaker is therefore not the normal, code-conforming practice for these small conductors.

12 AWG copper ampacity from NEC Table 310.16 (≤3 current-carrying conductors, 30°C ambient) is 20 A at 60°C, 25 A at 75°C, and 30 A at 90°C. The small-conductor rule, not the 90°C column, is what usually sets the 20 A device.

QuestionTypical resultPrimary references
Minimum copper size on a 20 A breaker12 AWG copper240.4(D); Table 310.16
May 14 AWG copper be used on a 20 A breaker?Generally no240.4(D) 15 A limit for 14 AWG copper
Type NM-B copper on a 20 A circuit12 AWG334.80 (60°C column) and 240.4(D)
12 AWG aluminum on a 20 A breakerGenerally no (15 A limit)240.4(D) for 12 AWG aluminum
Typical aluminum size if used on 20 AOften 10 AWG aluminum (confirm terminations and listing)240.4(D) 25 A limit for 10 AWG aluminum; 110.14

When 12 AWG may not be enough

A 20 A device does not automatically make 12 AWG the correct installed size. Consider at least the following:

  • Continuous loads. Where a load is continuous (3 hours or more), NEC 210.19 and 210.20 generally require conductor and overcurrent-device sizing at 125% of the continuous load. A 20 A circuit is therefore typically limited to 16 A of continuous load.
  • Voltage drop. The NEC does not generally make a specific voltage-drop percentage mandatory, but Informational Notes commonly discuss 3% on a branch circuit and 5% combined with the feeder as a design target. Long 20 A runs often use 10 AWG copper (or larger) to keep drop acceptable. Use the voltage drop calculator.
  • Ambient temperature, bundling, and rooftop conditions. Adjustment and correction factors can reduce allowable ampacity below 20 A for 12 AWG, which may require a larger conductor.
  • Equipment instructions and listings. An appliance or device may specify a minimum conductor size or a particular cable type.

More ampacity context is on the 12 AWG ampacity page and the NEC ampacity chart.

Disclaimer: This site is a general reference only. It is not a substitute for the adopted electrical code, manufacturer instructions, or the judgment of a licensed electrician. Ampacity, overcurrent protection, voltage drop, and conduit fill depend on conductor type, temperature rating, ambient temperature, the number of current-carrying conductors, termination ratings, installation method, and local amendments. Always verify figures in the edition of the code that applies to your work.