Voltage Drop Calculator
A client-side calculator for single-phase and three-phase conductor voltage drop, using the common 75°C K-factor formula and nominal circular-mil areas.
Calculate voltage drop
This tool estimates conductor voltage drop with the common 75°C K-factor method used in many US design references:
- Single-phase: VD = 2 × K × I × D / CM
- Three-phase: VD = 1.732 × K × I × D / CM
K is 12.9 Ω·cmil/ft for copper and 21.2 Ω·cmil/ft for aluminum (approximately 75°C). D is one-way circuit length in feet. CM is the conductor’s nominal circular-mil area. Current is the load current you enter, not the breaker rating, unless those happen to be the same. The result is an estimate; manufacturer DC or AC resistance (for example NEC Chapter 9, Tables 8 and 9) and operating temperature will produce a slightly different number.
Assumptions and limits
The K-factor method models conductor resistance at about 75°C and treats the circuit as a simple out-and-back (or equivalent three-phase) run at a single current. It does not include transformer or source impedance, motor starting current, power factor, or conduit magnetic effects beyond what is implicit in a simple K estimate. If the conductors operate much hotter or cooler than 75°C, actual drop will differ.
To choose a size that also meets ampacity and a drop target, use the wire size calculator.
Disclaimer: This site is a general reference only. It is not a substitute for the adopted electrical code, manufacturer instructions, or the judgment of a licensed electrician. Ampacity, overcurrent protection, voltage drop, and conduit fill depend on conductor type, temperature rating, ambient temperature, the number of current-carrying conductors, termination ratings, installation method, and local amendments. Always verify figures in the edition of the code that applies to your work.