Ampacity Chart (NEC)

Copper and aluminum ampacities from NEC Table 310.16 (formerly 310.15(B)(16)), for not more than three current-carrying conductors in a raceway, cable, or earth, at 30°C ambient.

NEC Table 310.16 conditions

The ampacities below are from NEC Table 310.16 (the same table formerly numbered 310.15(B)(16) in earlier editions). They apply to conductors rated 0 through 2000 volts, where not more than three current-carrying conductors are installed in a raceway, cable, or earth (directly buried), and the ambient temperature is 30°C (86°F).

Typical insulation types associated with each temperature column include:

  • 60°C: TW, UF
  • 75°C: RHW, THHW, THW, THWN, XHHW, USE, ZW
  • 90°C: THHN, THHW, THW-2, THWN-2, XHHW, XHHW-2, USE-2, and other 90°C types listed in the table

The column you may use is limited by the insulation rating and by termination ratings. Under NEC 110.14(C), equipment terminations are often selected from the 60°C or 75°C column even when the conductor insulation is rated 90°C. The 90°C column is commonly used as the starting point for adjustment and correction factors, after which the result must still not exceed the termination limit. Type NM-B cable is further limited by NEC 334.80 to the 60°C column for its allowable ampacity, even though the insulated conductors inside are typically 90°C rated.

Copper ampacities (A)

Values are in amperes. The last column restates the small-conductor overcurrent limits in NEC 240.4(D) where they apply. Those limits are separate from the table ampacity and generally govern ordinary branch-circuit breaker or fuse sizing for 14, 12, and 10 AWG copper.

Size (copper) 60°C (140°F) 75°C (167°F) 90°C (194°F) 240.4(D) OCPD max, if listed
14 AWG15202515 A
12 AWG20253020 A
10 AWG30354030 A
8 AWG405055—
6 AWG556575—
4 AWG708595—
3 AWG85100110—
2 AWG95115130—
1 AWG110130150—
1/0 AWG125150170—
2/0 AWG145175195—
3/0 AWG165200225—
4/0 AWG195230260—
250 kcmil215255290—
300 kcmil240285320—
350 kcmil260310350—
400 kcmil280335380—
500 kcmil320380430—
600 kcmil355420475—
750 kcmil400475535—
1000 kcmil455545615—

Aluminum and copper-clad aluminum ampacities (A)

Table 310.16 also lists aluminum and copper-clad aluminum. 240.4(D) generally limits 12 AWG aluminum to 15 A and 10 AWG aluminum to 25 A.

Size (aluminum) 60°C (140°F) 75°C (167°F) 90°C (194°F) 240.4(D) OCPD max, if listed
12 AWG15202515 A
10 AWG25303525 A
8 AWG354045—
6 AWG405060—
4 AWG556575—
3 AWG657585—
2 AWG7590100—
1 AWG85100115—
1/0 AWG100120135—
2/0 AWG115135150—
3/0 AWG130155175—
4/0 AWG150180205—
250 kcmil170205230—
300 kcmil190230255—
350 kcmil210250280—
400 kcmil225270305—
500 kcmil260310350—
600 kcmil285340385—
750 kcmil320385435—
1000 kcmil375445500—

What this table does not include

Free-air ampacities are in other 310.16-series tables (for example, Table 310.17 in recent editions) and are higher than the raceway values above. If there are more than three current-carrying conductors, NEC 310.15(C) (numbering varies by edition) requires adjustment. Ambient temperatures other than 30°C require the correction factors printed with Table 310.16. Continuous loads are generally calculated at 125% for conductor and overcurrent-device sizing (NEC 210.19, 210.20, and 215.2).

Related pages: 14 AWG ampacity, 12 AWG ampacity, 10 AWG ampacity, and 20 amp breaker wire size.

Disclaimer: This site is a general reference only. It is not a substitute for the adopted electrical code, manufacturer instructions, or the judgment of a licensed electrician. Ampacity, overcurrent protection, voltage drop, and conduit fill depend on conductor type, temperature rating, ambient temperature, the number of current-carrying conductors, termination ratings, installation method, and local amendments. Always verify figures in the edition of the code that applies to your work.