GFCI vs AFCI
A side-by-side reference for United States NEC practice: what a ground-fault circuit interrupter does, what an arc-fault circuit interrupter does, and how the two requirements differ.
Two different protective functions
In US National Electrical Code (NEC / NFPA 70) practice, a GFCI (ground-fault circuit interrupter) and an AFCI (arc-fault circuit interrupter) address different hazards. A GFCI is not a substitute for an AFCI, and an AFCI is not a substitute for a GFCI. Dual-function devices and combinations of breaker plus receptacle are used where both protections are required on the same circuit.
| GFCI | AFCI | |
|---|---|---|
| Primary hazard | Ground fault (current leaving the circuit conductors and returning through a person or another unintended path) | Dangerous arcing faults that can ignite nearby material |
| What it typically measures | Imbalance between the current in the ungrounded and grounded conductors (and other current paths of the device) | Current/voltage signatures associated with series and/or parallel arcing, depending on the device type |
| Personnel Class A trip level (UL 943) | Generally trips when ground-fault current is in the 4–6 mA range (Class A personnel protection) | Not a 4–6 mA personnel ground-fault device (unless it is a dual-function unit that also includes GFCI protection) |
| Common US product forms | Receptacle, breaker, dead-front, portable, and feeder devices, as listed | Circuit breaker (including combination-type), receptacle-type, and other listed forms |
| Typical NEC starting points | NEC 210.8 (GFCI protection for personnel) and related sections for specific equipment and feeders | NEC 210.12 (AFCI protection) and related sections |
Where the NEC requires them
The exact list of rooms, outlets, and equipment depends on the edition of the NEC adopted in the jurisdiction and on any local amendments. In broad terms:
- GFCI protection for personnel has long been required in bathrooms, outdoors, and certain other damp or readily accessible locations, and later editions expanded coverage (for example kitchens, basements, laundry areas, garages, indoor damp locations, and more receptacle outlets in dwellings). Equipment such as some boat hoists, vending machines, and other specific loads may have their own GFCI rules.
- AFCI protection in dwellings expanded from bedrooms to most 120 V dwelling-unit living-area branch circuits in later NEC editions (living rooms, closets, kitchens, laundry, and similar areas, depending on the edition). Combination-type AFCIs are the type generally referenced for that expansion.
Because 2020 and 2023 (and later) editions are not adopted uniformly, treat any location list on a reference site as a starting point and confirm the adopted Code. Manufacturer instructions and listing marks also matter: a device must be used where and how it is listed.
Testing and coordination
GFCI devices include a test function; manufacturers typically instruct periodic testing (often monthly). AFCI breakers also have a test feature. Nuisance trips can come from shared neutrals, damaged cords, moisture, or incompatible loads, but a trip is a reason to investigate, not to permanently bypass the device.
This page addresses US/NEC devices. Residual current devices used in BS 7671 and IEC practice are related in purpose to GFCIs but are specified differently (for example 30 mA additional protection, and Types AC, A, F, and B). See RCD types.
Disclaimer: This site is a general reference only. It is not a substitute for the adopted electrical code, manufacturer instructions, or the judgment of a licensed electrician. Ampacity, overcurrent protection, voltage drop, and conduit fill depend on conductor type, temperature rating, ambient temperature, the number of current-carrying conductors, termination ratings, installation method, and local amendments. Always verify figures in the edition of the code that applies to your work.